| = Introduction = | | = Introduction = |
| | | |
Line 7: |
Line 8: |
| <span style="font-size:medium;">Modbus Service is a Windows/Linux system service for WISE Agent to read sensor data from Modbus device or write data into Modbus device. After sensor data are acquired, WISE Agent will upload the data to the WISE-PaaS Cloud.</span> | | <span style="font-size:medium;">Modbus Service is a Windows/Linux system service for WISE Agent to read sensor data from Modbus device or write data into Modbus device. After sensor data are acquired, WISE Agent will upload the data to the WISE-PaaS Cloud.</span> |
| | | |
| + | |
| | | |
− | | + | |
| | | |
| = Features = | | = Features = |
Line 21: |
Line 23: |
| *<span style="font-size:medium;">Configurable sensor alias.</span> | | *<span style="font-size:medium;">Configurable sensor alias.</span> |
| *<font size="3">Support byte swap.</font> | | *<font size="3">Support byte swap.</font> |
− | *<span style="font-size:medium;">Currently support up-link Modbus Coil, Descrete input, Input register & Holding register data to WISE-PaaS , not support down-link from WISE-PaaS.</span> | + | *<span style="font-size:medium;">Support Modbus Coil, Descrete input, Input register & Holding register data.</span> |
| *<font size="3">Support maximal 10 links, 5 devices for each link, and 10 sensors for each device.</font> | | *<font size="3">Support maximal 10 links, 5 devices for each link, and 10 sensors for each device.</font> |
− | *<font size="3">Default data report interval: 100ms, configable sensor R/W interval, default is 1000ms. </font>
| |
| | | |
| = How to = | | = How to = |
| | | |
− | == Software Requirements == | + | == Login == |
− | | |
− | *<span style="font-size:medium;">MQTT broker ([https://www.dropbox.com/s/cijybdsex900737/MQTTBrokerSetup_1.0.4.exe?dl=0 download link])</span>
| |
− | *<span style="font-size:medium;">WISE Agent and enabled its connection with DeviceOn server </span>
| |
− | | |
− | == Installation ==
| |
| | | |
− | <span style="font-size:medium;">'''Windows:'''</span>
| + | Step 1. Launch a web browser (Google Chrome, Microsoft Edge ...) and open iEdge local web '''[http://127.0.0.1:8081 http://127.0.0.1:8081]''' |
| | | |
− | <span style="font-size:medium;">1. Download Modbus-Master for Windows from [http://ess-wiki.advantech.com.tw/view/Modbus-Master#Release Release] Table.</span>
| + | Step 2. Login iEdge local web: |
| | | |
− | <span style="font-size:medium;">2. Double click the installer to launch the installer to install it to the machine.</span>
| + | Account: '''root''' |
| | | |
− | <span style="font-size:medium;">'''Debian:'''</span>
| + | Password: '''P@ssw0rd''' |
| | | |
− | <span style="font-size:medium;">1. Download Modbus-Master for Debian from [http://ess-wiki.advantech.com.tw/view/Modbus_Master#Release Release] Table.</span>
| + | [[File:Ros2-iedge-plugin-config-01.png|frameless|900x520px|Ros2-iedge-plugin-config-01.png]] |
| | | |
− | <span style="font-size:medium;">2. Launch the installer to install it to the machine.</span>
| + | |
− | <pre>sudo ./device-modbus-master-3.0.1-Debian_9.9-rk3399.run
| |
− | </pre>
| |
| | | |
| == Configuration == | | == Configuration == |
| | | |
− | <span style="font-size:medium;">EdgeSense Modbus Master can manage multiple Modbus Slave setting and individual sensor's parameters, below settings are default after Modbus Master installation.</span>
| + | === How to config Model === |
− | | |
| | | |
| + | Step 1. Go to "Plug-ins" / Plugin Config to select Modbus-Master Plug-in |
| | | |
− | <span style="font-size:medium;">1. Device Configuration: <Install_folder>\config\industry\device-industry.yaml</span>
| + | [[File:Modbus config bQUoHri.png|border|800x480px|Modbus config bQUoHri.png]] |
− | <pre>metadata:
| |
− | name: "Modbus devices"
| |
− | labels: ["Modbus"]
| |
− | Description: "Modbus TCP/RTU devices with 3 sensors in holding register area 40001~40003"
| |
− | UpdateData: 2020-01-08-14:25:30
| |
| | | |
− | # LinkInfo: You can add a new link with unique name
| + | Setp 2. From Modbus-Master Configuration, open Model Management tab, click "+" to add new Model. |
− | # <LinkName>: Unique Link Name
| |
− | # Params: Serial Port or Network parameters
| |
− | # Info: Time interval of polling data & check link
| |
− | # DevList: Device list which defined in DeviceInfo section
| |
| | | |
− | LinkInfo:
| + | [[File:Modbus config qpMUDCj.png|border|800x480px|modbus_config_qpMUDCj.png]] |
− | TCP-IP-1:
| |
− | Params:
| |
− | Driver: Modbus-TCP
| |
− | ConnectType: Net
| |
− | IP: 127.0.0.1
| |
− | Port: 502
| |
− | Timeout: 1000 # A request timeout in milliseconds
| |
− |
| |
− | Info:
| |
− | PollingInterval: 3000 # Polling interval in milliseconds
| |
− | Retry: 3 # Count of retry min:0 max:3
| |
− | AliveTime: 10 # Link Timeout in second: SDK will release this link if there are any request over this AliveTime ( second )
| |
− | CheckLinkInterval: 2 # Check link status interval (second)
| |
| | | |
− | DevList:
| + | Setp 3. Input Model name and Description for new Model. |
− | - Device-1
| |
| | | |
− | COM1:
| + | [[File:Modbus config XLSJYyn.png|border|800x480px|modbus_config_XLSJYyn.png]] |
− | Params:
| |
− | Driver: Modbus-RTU
| |
− | ConnectType: Serial
| |
− | PortName: COM1
| |
− | BaudRate: 9600
| |
− | DataBits: 8
| |
− | StopBits: 1
| |
− | Parity: None
| |
− | Timeout: 1000 # A request timeout in milliseconds
| |
− |
| |
− | Info:
| |
− | PollingInterval: 3000 # Polling interval in milliseconds
| |
− | Retry: 3 # Count of retry min:0 max:3
| |
− | AliveTime: 10 # Link Timeout in second: SDK will release this link if there are any request over this AliveTime ( second )
| |
− | CheckLinkInterval: 2 # Check link status interval (second)
| |
| | | |
− | DevList: | + | Step 4. Click "+" to add Sensor - Input Sensor Name - Select Address Space, Access mode, Data Type, Data Format and input Address, Data Length, Minimal/Maximal Value for new sensor's attributes. - Input below timing attributes: Period (second) . Delay (ms, range: 0~1000ms) and Retry (range: 0~5) |
− | - Device-2 | |
| | | |
| + | *Click "Save" button to save the new sensor. |
| | | |
− | # DeviceInfo: You can add a new device with unique name
| + | [[File:Modbus config qsox6hM.png|border|800x480px|modbus_config_qsox6hM.png]] |
− | # <DeviceName>: Unique Device Name
| |
− | # Params: Station number
| |
− | # Profile: Profile file name
| |
| | | |
− | DeviceInfo:
| + | Step 5. Repeat Step 4 to add another sensor. |
− | Device-1:
| |
− | Params:
| |
− | Station: 1
| |
| | | |
− | Profile: MODBUS_DEVICE_01.yaml
| + | [[File:Modbus config DPdBICk.png|border|800x480px|modbus_config_DPdBICk.png]] |
| | | |
− | Device-2:
| + | Step 6. Click "Save" button to save the new sensors. |
− | Params:
| |
− | Station: 2
| |
| | | |
− | Profile: MODBUS_DEVICE_02.yaml
| + | [[File:Modbus config oXbCCsc.png|border|800x480px|modbus_config_oXbCCsc.png]] |
| | | |
− | </pre>
| + | Step 5. Click "Save" button to save the new model. |
| | | |
| + | [[File:Modbus config kXoLU5M.png|border|800x480px|modbus_config_kXoLU5M.png]] |
| | | |
| + | <br/> |
| | | |
− | <span style="font-size:medium;">2. Sensor Configuration for Device-1: <Install_folder>\config\industry\Profile\MODBUS_DEVICE_01.yaml</span>
| + | === How to config Link === |
− | <pre>
| |
− | metadata:
| |
− | name: MODBUS_DEVICE_01.yaml
| |
− | labels: ["MODBUS"]
| |
− | Description: This profile is for Modbus device 01
| |
− | version: 1.0.1
| |
− | UpdateData: 2020-01-08-14:25:30
| |
| | | |
− | Sensor:
| + | Step 1. From Modbus-Master Configuration, open Link Management tab, click "+" to add a new Link. |
− | Temperature:
| |
− | Params:
| |
− | Address: 0 # Address
| |
− | Length: 1
| |
− | DataType: int16
| |
− | DataFormat: ABCD
| |
| | | |
− | Info:
| + | [[File:Modbus config Sz3fL8f.png|border|800x480px|modbus_config_Sz3fL8f.png]] |
− | v: -1
| |
− | asm: rw # Access Right: r, w, rw
| |
− | min: -10 # Minimum Value
| |
− | max: 100 # Maximum Value
| |
− | u: "celsius" # Unit
| |
| | | |
− | Humidity:
| + | Step 2. Input Link Name, Link Type for the new Link. |
− | Params:
| |
− | Address: 1
| |
− | Length: 1
| |
− | DataType: int16
| |
− | DataFormat: ABCD
| |
| | | |
− | Info:
| + | for Modbus-TCP link, set parameters: - IP - Port |
− | v: -1
| |
− | asm: rw # Access Right: r, w, rw
| |
− | min: 0 # Minimum Value
| |
− | max: 100 # Maximum Value
| |
− | u: "percent" # Unit
| |
| | | |
− | </pre>
| + | for Modbus-RTU link, set parameters: - COM port - Baudrate - Data bits - Stop bits - Parity mode |
| | | |
| + | Click "+" icon to add a new device. |
| | | |
| + | [[File:Modbus config Dvkgjc2.png|border|800x480px|modbus_config_Dvkgjc2.png]] |
| | | |
− | <span style="font-size:medium;">2. Sensor Configuration for Device-2: <Install_folder>\config\industry\Profile\MODBUS_DEVICE_02.yaml</span>
| + | Step 3. Input Device Name, Station Id and select Model Profile for the new device. Model Profile should be added by upper Model Management steps. |
− | <pre>metadata:
| |
− | name: MODBUS_DEVICE_02.yaml
| |
− | labels: ["MODBUS"]
| |
− | Description: This profile is for Modbus device 02
| |
− | version: 1.0.1
| |
− | UpdateData: 2020-01-08-14:25:30
| |
| | | |
− | Sensor:
| + | Click "Save" button to save the new device. |
− | X-Axis:
| |
− | Params:
| |
− | Address: 0 # Address
| |
− | Length: 1
| |
− | DataType: int16
| |
− | DataFormat: ABCD
| |
| | | |
− | Info:
| + | [[File:Modbus config CkZoH3H.png|border|800x480px|modbus_config_CkZoH3H.png]] |
− | v: -1
| |
− | asm: rw # Access Right: r, w, rw
| |
− | min: -10 # Minimum Value
| |
− | max: 100 # Maximum Value
| |
− | u: "mm/sec" # Unit
| |
| | | |
− | Y-Axis:
| + | Step 4. Click "Save" button to save the new link. |
− | Params:
| |
− | Address: 1
| |
− | Length: 1
| |
− | DataType: int16
| |
− | DataFormat: ABCD
| |
| | | |
− | Info:
| + | [[File:Modbus config jGIBhIa.png|border|800x480px|modbus_config_jGIBhIa.png]] |
− | v: -1
| |
− | asm: rw # Access Right: r, w, rw
| |
− | min: -100 # Minimum Value
| |
− | max: 100 # Maximum Value
| |
− | u: "mm/sec" # Unit
| |
| | | |
− | </pre>
| + | Step 5. Click "Apply" button to apply the new link. |
| | | |
− | = Demonstration =
| + | [[File:Modbus config YudsLa4.png|border|800x480px|modbus_config_YudsLa4.png]] |
| | | |
− | <span style="font-size:medium;">1. Open Modbus Simulator: Launch [https://www.win-tech.com/html/modsim32.htm ModSim32] and click "New" in program menu to create a new simulator page.</span>
| + | Apply new settings Successfully |
| | | |
− | [[File:Modbus-Slave Modsim32 04.png|border|700x400px|Modbus-Slave Modsim32 04.png]] | + | [[File:Modbus config 7rvJoo5.png|border|800x480px|modbus_config_7rvJoo5.png]] |
| | | |
| + | Step 6. Go to Plugin List and select Modbus-Master plugin, the new sensor will be shown in this page |
| | | |
| + | [[File:Modbus config Sys1ZZH.png|border|800x480px|modbus_config_Sys1ZZH.png]] |
| | | |
− | <span style="font-size:medium;">2. Set parameter as below:</span> | + | <br/> |
| | | |
− | *<span style="font-size:medium;">Device Id: 1</span>
| + | === How to import plugin settings === |
− | *<span style="font-size:medium;">Address: 0001</span>
| |
− | *<span style="font-size:medium;">Length: 2</span>
| |
− | *<span style="font-size:medium;">Modbus Point Type: INPUT REGISTER</span>
| |
| | | |
− | <span style="font-size:medium;">[[File:Modsim-ir-01.png|520x400px|Modbus-Slave Modsim32 01.png]]</span>
| + | Step 1. Click Import button from Modbus-Master Configuration |
| | | |
| + | [[File:Modbus config T6zjSoj.png|border|800x480px|modbus_config_T6zjSoj.png]] |
| | | |
| + | Step 2. Select target file you like to import |
| | | |
− | <span style="font-size:medium;">3. Enable Auto Simulation:</span>
| + | [[File:Modbus config ZYeZTw5.png|border|800x480px|modbus_config_ZYeZTw5.png]] |
| | | |
− | *<span style="font-size:medium;">Double click on the sensor address 30001</span>
| + | Import successful |
− | *<span style="font-size:medium;">Click "Auto Simulation"</span>
| |
| | | |
| + | [[File:Modbus config k3N8BQO.png|border|800x480px|modbus_config_k3N8BQO.png]] |
| | | |
| + | Step 3. Click APPLY to use imported configuration |
| | | |
− | [[File:Modbus-Slave Modsim32 02.png|300x200px|Modbus-Slave Modsim32 02.png]] | + | [[File:Modbus config JTgo9CB.png|border|800x480px|modbus_config_JTgo9CB.png]] |
| | | |
| + | Apply new settings Successfully |
| | | |
| + | [[File:Modbus config WZGsmXR.png|border|800x480px|modbus_config_WZGsmXR.png]] |
| | | |
| + | <br/> |
| | | |
| + | === How to export plugin settings === |
| | | |
− | <span style="font-size: medium;">4. Set simulation parameters:</span>
| + | Step 1. Click Export button from Modbus-Master Configuration |
| | | |
− | *<span style="font-size:medium;">Check "Enable"</span>
| + | [[File:Modbus config tH3zFyI.png|border|800x480px|modbus_config_tH3zFyI.png]] |
− | *<span style="font-size:medium;">Simulation Type: Increment</span>
| |
− | *<span style="font-size:medium;">Change Interval (secs): 5</span>
| |
− | *<span style="font-size:medium;">Step VAlue: 1</span>
| |
− | *<span style="font-size:medium;">Low Limit: 10</span>
| |
− | *<span style="font-size:medium;">High Limit: 20</span>
| |
| | | |
− | [[File:Modbus-Slave Modsim32 03.png|360x280px|Modbus-Slave Modsim32 03.png]]
| + | Step 2. Explore the exported file |
| | | |
| + | [[File:Modbus config IU83MxX.png|border|800x480px|modbus_config_IU83MxX.png]] |
| | | |
| + | <br/> |
| | | |
− | <span style="font-size:medium;">5. Do the same step for the address 30002 and set simulation parameter as below:</span>
| + | == Use case == |
| | | |
− | *<span style="font-size:medium;">Simulation Type: Increment</span>
| + | === Connect and upload data for Modbus Temperature and Humidity sensor === |
− | *<span style="font-size:medium;">Low Limit: 60</span>
| |
− | *<span style="font-size:medium;">High Limit: 80</span>
| |
| | | |
− | <span style="font-size:medium;">[[File:Modbus-Slave Modsim32 05.png|360x280px|Modbus-Slave Modsim32 05.png]]</span>
| + | Use Modsim32 to simulate a modbus TCP device with a temperature sensor and a humidity sensor, config Modbus-Master to read these two sensors and upload iEdge cloud. |
| | | |
| + | |
| | | |
| + | |
| | | |
| + | ==== Config Modbus simulator ==== |
| | | |
| + | Step1. Open Modbus Simulator: Launch ModSim32 and click "New" in program menu to create a new simulator page. |
| | | |
− | <span style="font-size:medium;">6. Set Connection to Modbus/TCP Svr:</span>
| + | [[File:Modbus config GskBtAL.png|800x480px|Modbus config GskBtAL.png]] |
| | | |
− | <span style="font-size:medium;">[[File:Modsim-ir-02.png|520x400px|Modbus-Slave Modsim32 06.png]]</span>
| + | Step2. Set parameter as below: |
| | | |
| + | *Device Id: '''1''' |
| + | *Address: '''0001''' |
| + | *Length: '''2''' |
| + | *Modbus Point Type: '''INPUT REGISTER''' |
| | | |
| + | [[File:Modbus config wVMbXWs.png|800x480px|Modbus config wVMbXWs.png]] |
| | | |
| + | Step3. Enable Auto Simulation: |
| | | |
| + | *Double click on the sensor address 30001 |
| + | *Click "Auto Simulation" |
| | | |
| + | [[File:Modbus config PaxcEE3.png|320x200px|Modbus config PaxcEE3.png]] |
| | | |
| + | Step4. Set simulation parameters: |
| | | |
− | <span style="font-size:medium;">7. Edit Device Configuration for the demo: <Install_folder>\config\industry\device-industry.yaml</span>
| + | *Check "Enable" |
− | <pre>metadata:
| + | *Simulation Type: Increment |
− | name: "Modbus devices"
| + | *Change Interval (secs): 5 |
− | labels: ["Modbus"]
| + | *Step VAlue: 1 |
− | Description: "Modbus TCP/RTU devices with 3 sensors in holding register area 40001~40003"
| + | *Low Limit: 10 |
− | UpdateData: 2020-01-08-14:25:30
| + | *High Limit: 20 |
| | | |
− | # LinkInfo: You can add a new link with unique name
| + | [[File:Modbus config maLqhtS.png|600x320px|Modbus config maLqhtS.png]] |
− | # <LinkName>: Unique Link Name
| |
− | # Params: Serial Port or Network parameters
| |
− | # Info: Time interval of polling data & check link
| |
− | # DevList: Device list which defined in DeviceInfo section
| |
| | | |
− | LinkInfo:
| + | Step5. Do the same step for the address 30002 and set simulation parameter as below: |
− | TCP-IP-1:
| |
− | Params:
| |
− | Driver: Modbus-TCP
| |
− | ConnectType: Net
| |
− | IP: 127.0.0.1
| |
− | Port: 502
| |
− | Timeout: 1000 # A request timeout in milliseconds
| |
− |
| |
− | Info:
| |
− | PollingInterval: 3000 # Polling interval in milliseconds
| |
− | Retry: 3 # Count of retry min:0 max:3
| |
− | AliveTime: 10 # Link Timeout in second: SDK will release this link if there are any request over this AliveTime ( second )
| |
− | CheckLinkInterval: 2 # Check link status interval (second)
| |
| | | |
− | DevList:
| + | *Simulation Type: Decrement |
− | - Device-1
| + | *Change Interval (secs): 5 |
| + | *Step VAlue: 1 |
| + | *Low Limit: 60 |
| + | *High Limit: 80 |
| | | |
− | </pre>
| + | [[File:Modbus config K98RWgN.png|600x320px|Modbus config K98RWgN.png]] |
| | | |
| + | Step6. Set Connection to Modbus/TCP Svr: |
| | | |
| + | *Click Connection |
| + | *Click Modbus/TCP Svr to simulate Modbus TCP connection |
| | | |
− | <span style="font-size:medium;">8. Edit Sensor Configuration for the demo: <Install_folder>\config\industry\Profile\MODBUS_DEVICE_01.yaml</span>
| + | [[File:Modbus config ZhpooZd.png|800x480px|Modbus config ZhpooZd.png]] |
− | <pre>metadata:
| |
− | name: MODBUS_DEVICE_01.yaml
| |
− | labels: ["MODBUS"]
| |
− | Description: This profile is for Modbus device 01
| |
− | version: 1.0.1
| |
− | UpdateData: 2020-01-08-14:25:30
| |
| | | |
− | Sensor:
| + | Step7. Config Modbus-Master |
− | Temperature:
| |
− | Params:
| |
− | Address: 0 # Address
| |
− | Length: 1
| |
− | DataType: int16
| |
− | DataFormat: ABCD
| |
| | | |
− | Info:
| + | *Config Modbus-Master plugin as upper steps to complete the settings. |
− | v: -1
| |
− | asm: r # Access Right: r, w, rw
| |
− | min: -10 # Minimum Value
| |
− | max: 100 # Maximum Value
| |
− | u: "celsius" # Unit
| |
| | | |
− | Humidity: | + | |
− | Params: | |
− | Address: 1
| |
− | Length: 1
| |
− | DataType: int16
| |
− | DataFormat: ABCD
| |
− | | |
− | Info:
| |
− | v: -1
| |
− | asm: r # Access Right: r, w, rw
| |
− | min: 0 # Minimum Value
| |
− | max: 100 # Maximum Value
| |
− | u: "percent" # Unit
| |
− | | |
− | <span style="font-size:medium;">9. Restart Modbus Master services</span></pre>
| |
− | | |
− | | |
− | | |
− | *<span style="font-size:medium;">Open Windows Task Manager</span>
| |
− | *<span style="font-size:medium;">Restart service: device-modbus-protocol</span>
| |
− | *<span style="font-size:medium;">Restart service: device-modbus-master</span>
| |
− | | |
− | | |
− | | |
− | | |
− | | |
− | <span style="font-size:medium;">10. Verify sensor data at DeviceOn Monitor Sensor Data page</span>
| |
− | | |
− | [[File:Modbus-Slave Modsim32 07.png|border|800x400px|Modbus-Slave Modsim32 07.png]]
| |
− | | |
− | = Release =
| |
− | | |
− | <span style="font-size:larger;">This is an overview that displays Modbus Service versions and some stats and numbers for each release.</span>
| |
− | | |
− | {| border="1" cellspacing="1" cellpadding="1" style="width: 1203px;"
| |
− | |-
| |
− | | style="width: 47px; text-align: center;" | <span style="font-size:larger;">Index</span>
| |
− | | style="width: 63px; text-align: center;" | <span style="font-size:larger;">Version</span>
| |
− | | style="width: 85px; text-align: center;" | <span style="font-size:larger;">Date</span>
| |
− | | style="width: 78px; text-align: center;" | <span style="font-size:larger;">Platform</span>
| |
− | | style="width: 103px; text-align: center;" | <span style="font-size:larger;">OS</span>
| |
− | | style="width: 433px; text-align: center;" | <span style="font-size:larger;">Release Note</span>
| |
− | | style="width: 357px; text-align: center;" | <span style="font-size:larger;">Installer</span>
| |
− | |-
| |
− | | style="width: 47px; text-align: center;" | <span style="font-size:larger;">1</span>
| |
− | | style="width: 63px; text-align: center;" | <span style="font-size:larger;">v3.0.1</span>
| |
− | | style="width: 85px; text-align: center;" |
| |
− | <font size="3">2020/01/21</font>
| |
− | | |
− | | style="width: 78px; text-align: center;" | <span style="font-size:larger;">x86_64 CPU</span><br/>
| |
− | | style="width: 103px; text-align: center;" | <span style="font-size:larger;">Windows 10</span><br/>
| |
− | | style="width: 433px;" |
| |
− | *<span style="font-size:medium; text-align: left;">Support connection for multiple Modbus slave.</span>
| |
− | *<span style="font-size:medium; text-align: left;">Support Modbus TCP and RTU in one configuration.</span>
| |
− | *<span style="font-size:medium; text-align: left;">Support individual read interval by connection.</span>
| |
− | *<span style="font-size:medium; text-align: left;">Support only get Modbus data.</span>
| |
− | | |
− | | style="width: 357px;" | <span style="font-size:larger;">[file://eossfs/ESS-Release/EdgeSense/Software/Modbus-Master device-modbus-master-3.0.1.exe]</span>
| |
− | |-
| |
− | | style="width: 47px; text-align: center;" | <span style="font-size:larger;">2</span>
| |
− | | style="width: 63px; text-align: center;" | <span style="font-size:larger;">v3.0.1</span>
| |
− | | style="width: 85px; text-align: center;" |
| |
− | <font size="3">Coming soon</font>
| |
− | | |
− | | style="width: 78px; text-align: center;" | <span style="font-size:larger;">ARM CPU</span><br/>
| |
− | | style="width: 103px; text-align: center;" | <span style="font-size:larger;">Debian</span><br/>
| |
− | | style="width: 433px;" |
| |
− | *<span style="font-size:medium; text-align: left;">Support connection for multiple Modbus slave.</span>
| |
− | *<span style="font-size:medium; text-align: left;">Support Modbus TCP and RTU in one configuration.</span>
| |
− | *<span style="font-size:medium; text-align: left;">Support individual read interval by connection.</span>
| |
− | *<span style="font-size:medium; text-align: left;">Support only get Modbus data.</span>
| |
− | | |
− | | style="width: 357px;" | <span style="font-size:larger;">[file://eossfs/ESS-Release/EdgeSense/Software/Modbus-Master device-modbus-master-3.0.1-Debian_9.9-rk3399.run]</span>
| |
− | |-
| |
− | | style="width: 47px; text-align: center;" | <span style="font-size:larger;">3</span>
| |
− | | style="width: 63px; text-align: center;" | <span style="font-size:larger;">v3.0.2</span>
| |
− | | style="width: 85px; text-align: center;" |
| |
− | <font size="3">2020/02/17</font>
| |
− | | |
− | | style="width: 78px; text-align: center;" | <span style="font-size:larger;">x86_64 CPU</span><br/>
| |
− | | style="width: 103px; text-align: center;" | <span style="font-size:larger;">Windows 10</span><br/>
| |
− | | style="width: 433px;" |
| |
− | *<span style="font-size:medium; text-align: left;">Support network link lost-reconnect feature.</span>
| |
− | *<span style="font-size:medium; text-align: left;">Support serial port link lost-reconnect feature.</span>
| |
− | *<span style="font-size:medium; text-align: left;">Support modbus slave lost-reconnect feature.</span>
| |
− | *<span style="font-size:medium; text-align: left;">Support resume from S3/S4 feature.</span>
| |
− | | |
− | | style="width: 357px;" | <span style="font-size:larger;">[file://eossfs/ESS-Release/EdgeSense/Software/Modbus-Master device-modbus-master-3.0.2.exe]</span>
| |
− | |-
| |
− | | style="width: 47px; text-align: center;" | <span style="font-size:larger;">4</span>
| |
− | | style="width: 63px; text-align: center;" | <span style="font-size:larger;">v3.0.2</span>
| |
− | | style="width: 85px; text-align: center;" |
| |
− | <font size="3">2020/02/17</font>
| |
− | | |
− | | style="width: 78px; text-align: center;" | <span style="font-size:larger;">ARM CPU</span><br/>
| |
− | | style="width: 103px; text-align: center;" | <span style="font-size:larger;">Debian</span><br/>
| |
− | | style="width: 433px;" |
| |
− | *<span style="font-size:medium; text-align: left;">Support network link lost-reconnect feature.</span>
| |
− | *<span style="font-size:medium; text-align: left;">Support serial port link lost-reconnect feature.</span>
| |
− | *<span style="font-size:medium; text-align: left;">Support modbus slave lost-reconnect feature.</span>
| |
− | *<span style="font-size:medium; text-align: left;">Support resume from S3/S4 feature.</span>
| |
− | | |
− | | style="width: 357px;" | <span style="font-size:larger;">[file://eossfs/ESS-Release/EdgeSense/Software/Modbus-Master device-modbus-master-3.0.2-Debian_9.9-rk3399.run]</span>
| |
− | |}
| |
− | | |
− | <span style="font-size:larger;">Above files are available at local server, please paste file's url in File Explorer to copy file. ([[EdgeSense_FAQ|How to access to EOSSFS file server]] )</span>
| |