Difference between revisions of "Modbus Service"

From ESS-WIKI
Jump to: navigation, search
Line 1: Line 1:
= <span style="font-size:x-large;">Release</span> =
+
= Release =
  
 
<span style="font-size:large;">Agent_Modbus_Handler_2.0.0-rc1</span>
 
<span style="font-size:large;">Agent_Modbus_Handler_2.0.0-rc1</span>
  
<span style="font-size:large;"></span>
+
 
  
  
Line 41: Line 41:
 
<span style="font-size:large;">[[File:Agent modbus handler 06.png|800x600px|Agent modbus handler 06.png]]</span>
 
<span style="font-size:large;">[[File:Agent modbus handler 06.png|800x600px|Agent modbus handler 06.png]]</span>
  
<span style="font-size:x-large;"></span>
+
 
  
 
== <span style="font-size:x-large;">Configuration</span> ==
 
== <span style="font-size:x-large;">Configuration</span> ==
Line 138: Line 138:
 
B2=2,LED2
 
B2=2,LED2
 
</pre>
 
</pre>
 
 
  
  
Line 161: Line 159:
 
IB2=2,Switch2</pre>
 
IB2=2,Switch2</pre>
  
<span style="font-size:x-large;"></span>
 
  
= EdgeSense Linux Docker version =
+
 
 +
 
 +
 
 +
= <span style="font-size:x-large;">EdgeSense Linux Docker version</span> =
  
 
=== '''How to config&nbsp;Modbus Service and Restart Service''' ===
 
=== '''How to config&nbsp;Modbus Service and Restart Service''' ===
Line 176: Line 176:
  
  
 
+
= JSON Format for upload data =
 
 
 
 
= <span style="font-size:x-large;">JSON Format for upload data</span> =
 
 
<pre>{
 
<pre>{
 
&nbsp; &nbsp;"Modbus_Handler":{
 
&nbsp; &nbsp;"Modbus_Handler":{

Revision as of 11:27, 7 May 2018

Release

Agent_Modbus_Handler_2.0.0-rc1





Installation

1. Double click Agent_Modbus_Handler_2.0.0.exe to start installation.

2. Click "Next" on the Welcome screen.

Agent modbus handler 02.png



3. Select Installation Folder and then click "Next" to continue.

Agent modbus handler 03.png



4. Click "Install" on the Ready to Install screen to continue.

Agent modbus handler 04.png


5. Installation completed, click "Finish" button to exit the Setup Wizard.

Agent modbus handler 06.png


Configuration

1. Open File Explorer and change target folder to the Modbus Service installation folder.

2. Open and edit the file Mobus_Handler.ini

2.1 Give a Name for the platform.

2.2 Set the Protocol.

For the modbus TCP devices:

Protocol=Modbus_TCP

ClientIP=(IP address of Modbus TCP devices)

ClientPort=(Port of Modbus TCP devices)  

Example:

[Platform]
Name=WISE-4012E
Protocol=Modbus_TCP
ClientIP=127.0.0.1
ClientPort=502

Interval=3
#Interval: The time delay between two modbus access round in second.
Delay=0
#Delay: The time delay between two modbus access in millisecond.
#Delay=0 means no delay.
Log=0



For the modbus RTU devices:

Protocol=Modbus_RTU

SlavePort=(The serial port's device node of the gateway which connect to Modbus RTU devices)

Baud=(The baud rate of the serial port)

Parity=(The parity of the serial port)

DataBits=(The data bits of the serial port)              

StopBits=(The stop bits of the serial port) 


Example:

[Platform]
Name=EKI-XXXX
Protocol=Modbus_RTU
SlavePort=COM1
Baud=19200
Parity=None
DataBits=8
StopBits=1

Interval=3
#Interval: The time delay between two modbus access round in second.
Delay=0
#Delay: The time delay between two modbus access in millisecond.
#Delay=0 means no delay.
Log=0



2.3 Set the number of modbus devices and device detail information file.

Device0 Example:

[DeviceInfo]
Name=Modbus_Device0

# For Modbus_TCP
UnitID=1

# For Modbus_RTU
#SlaveID=1

[Coils]
numberOfB=3
B0=0,LED0
B1=1,LED1
B2=2,LED2



Device1 Example:

[DeviceInfo]
Name=Modbus_Device1

# For Modbus_TCP
UnitID=2

# For Modbus_RTU
#SlaveID=2

[Discrete Inputs]
numberOfIB=3
IB0=0,Switch0
IB1=1,Switch1
IB2=2,Switch2



EdgeSense Linux Docker version

How to config Modbus Service and Restart Service

$cd ${Installed path}/Installer/packages/Plugins/docker-edgesense-image-x86/EdgeSense/EService-Modbus/config
$sudo vim Modbus_Handler.ini
$sudo docker restart service-modbus




JSON Format for upload data

{
   "Modbus_Handler":{
      "Platform":{
         "bn":"Platform",
         "e":[{"n":"Version","sv":"2.0.0"},
              {"n":"Description","sv":"This service is Modbus Service"},
              {"n":"Protocol","sv":"Modbus_TCP"},
              {"n":"Name","sv":"WISE-4012E"},
              {"n":"ClientIP","sv":"127.0.0.1"},
              {"n":"ClientPort","sv":"502"},
              {"n":"Connection","bv":true}]
      },
      "Modbus_Device0":{
         "bn":"Modbus_Device0",
         "e":[{"n":"UnitID","sv":"1"}],
         "Coils":{
            "bn":"Coils",
            "e":[{"n":"LED0","bv":true},
                 {"n":"LED1","bv":true},
                 {"n":"LED2","bv":false}]
         }
      },
      "Modbus_Device1":{
         "bn":"Modbus_Device1",
         "e":[{"n":"UnitID","sv":"2"}],
         "Discrete Inputs":{
            "bn":"Discrete Inputs",
            "e":[{"n":"Switch0","bv":false},
                 {"n":"Switch1","bv":true},
                 {"n":"Switch2","bv":false}]
         }
      }
   }
}