Difference between revisions of "Modbus Service"
Line 77: | Line 77: | ||
− | + | ||
<span style="font-size:larger;">'''<u>For the modbus RTU devices:</u>'''</span> | <span style="font-size:larger;">'''<u>For the modbus RTU devices:</u>'''</span> | ||
Line 95: | Line 95: | ||
− | + | ||
'''<span style="font-size:larger;">Example:</span>''' | '''<span style="font-size:larger;">Example:</span>''' | ||
Line 120: | Line 120: | ||
− | + | ||
<span style="font-size:large;">2.3 Set the number of modbus devices and device detail information file.</span> | <span style="font-size:large;">2.3 Set the number of modbus devices and device detail information file.</span> | ||
Line 144: | Line 144: | ||
− | + | ||
'''<span style="font-size:larger;">Device1 Example:</span>''' | '''<span style="font-size:larger;">Device1 Example:</span>''' | ||
Line 163: | Line 163: | ||
<span style="font-size:larger;"></span><span style="font-size:larger;"> | <span style="font-size:larger;"></span><span style="font-size:larger;"> | ||
</span></pre> | </span></pre> | ||
+ | |||
+ | |||
+ | |||
+ | |||
= EdgeSense Linux Docker version = | = EdgeSense Linux Docker version = | ||
Line 171: | Line 175: | ||
$sudo docker restart service-modbus | $sudo docker restart service-modbus | ||
</pre> | </pre> | ||
+ | |||
+ | |||
Revision as of 05:52, 7 May 2018
Contents
Installation
1. Double click Agent_Modbus_Handler_2.0.0.exe to start installation.
2. Click "Next" on the Welcome screen.
3. Select Installation Folder and then click "Next" to continue.
4. Click "Install" on the Ready to Install screen to continue.
5. Installation completed, click "Finish" button to exit the Setup Wizard.
Configuration
1. Open File Explorer and change target folder to the Modbus Service installation folder.
2. Open and edit the file Mobus_Handler.ini
2.1 Give a Name for the platform.
2.2 Set the Protocol.
For the modbus TCP devices:
Protocol=Modbus_TCP
ClientIP=(IP address of Modbus TCP devices)
ClientPort=(Port of Modbus TCP devices)
Example:
<span style="font-size:larger;">[Platform] Name=WISE-4012E Protocol=Modbus_TCP ClientIP=127.0.0.1 ClientPort=502 Interval=3 #Interval: The time delay between two modbus access round in second. Delay=0 #Delay: The time delay between two modbus access in millisecond. #Delay=0 means no delay. Log=0 </span>
For the modbus RTU devices:
Protocol=Modbus_RTU
SlavePort=(The serial port's device node of the gateway which connect to Modbus RTU devices)
Baud=(The baud rate of the serial port)
Parity=(The parity of the serial port)
DataBits=(The data bits of the serial port)
StopBits=(The stop bits of the serial port)
Example:
<span style="font-size:larger;">[Platform] Name=EKI-XXXX Protocol=Modbus_RTU SlavePort=COM1 Baud=19200 Parity=None DataBits=8 StopBits=1 Interval=3 #Interval: The time delay between two modbus access round in second. Delay=0 #Delay: The time delay between two modbus access in millisecond. #Delay=0 means no delay. Log=0 </span>
2.3 Set the number of modbus devices and device detail information file.
Device0 Example:
<span style="font-size:larger;">[DeviceInfo] Name=Modbus_Device0 # For Modbus_TCP UnitID=1 # For Modbus_RTU #SlaveID=1 [Coils] numberOfB=3 B0=0,LED0 B1=1,LED1 B2=2,LED2</span><span style="font-size:larger;"> </span>
Device1 Example:
<span style="font-size:larger;">[DeviceInfo] Name=Modbus_Device1 # For Modbus_TCP UnitID=2 # For Modbus_RTU #SlaveID=2 [Discrete Inputs] numberOfIB=3 IB0=0,Switch0 IB1=1,Switch1 IB2=2,Switch2</span> <span style="font-size:larger;"></span><span style="font-size:larger;"> </span>
EdgeSense Linux Docker version
How to config Modbus Service and Restart Service
$cd ${Installed path}/Installer/packages/Plugins/docker-edgesense-image-x86/EdgeSense/EService-Modbus/config $sudo vim Modbus_Handler.ini $sudo docker restart service-modbus
JSON Format for upload data
{ "Modbus_Handler":{ "Platform":{ "bn":"Platform", "e":[{"n":"Version","sv":"2.0.0"}, {"n":"Description","sv":"This service is Modbus Service"}, {"n":"Protocol","sv":"Modbus_TCP"}, {"n":"Name","sv":"WISE-4012E"}, {"n":"ClientIP","sv":"127.0.0.1"}, {"n":"ClientPort","sv":"502"}, {"n":"Connection","bv":true}] }, "Modbus_Device0":{ "bn":"Modbus_Device0", "e":[{"n":"UnitID","sv":"1"}], "Coils":{ "bn":"Coils", "e":[{"n":"LED0","bv":true}, {"n":"LED1","bv":true}, {"n":"LED2","bv":false}] } }, "Modbus_Device1":{ "bn":"Modbus_Device1", "e":[{"n":"UnitID","sv":"2"}], "Discrete Inputs":{ "bn":"Discrete Inputs", "e":[{"n":"Switch0","bv":false}, {"n":"Switch1","bv":true}, {"n":"Switch2","bv":false}] } } } }
Modbus Configuration Template
Modbus_Handler.ini
[Platform] Name=WISE-4012E Protocol=Modbus_TCP ClientIP=127.0.0.1 ClientPort=502 UnitID=1 Interval=3 #Interval: The time delay between two modbus access round in second. Delay=0 #Delay: The time delay between two modbus access in millisecond. #Delay=0 means no delay. Log=0 #Name=EKI-XXXX #Protocol=Modbus_RTU #SlavePort=COM1 #Baud=19200 #Parity=None #DataBits=8 #StopBits=1 [Devices] numberOfDevices=2 Device0=Modbus_Device0 Device1=Modbus_Device1
Modbus_Device0.ini
[DeviceInfo] Name=Modbus_Device0 # For Modbus_TCP UnitID=1 [Coils] numberOfB=3 B0=0,LED0 B1=1,LED1 B2=2,LED2
Modbus_Device1.ini
[DeviceInfo] Name=Modbus_Device1 # For Modbus_TCP UnitID=2 [Discrete Inputs] numberOfIB=3 IB0=0,Switch0 IB1=1,Switch1 IB2=2,Switch2