Line 137: |
Line 137: |
| = Real Application Case - ADAM-4117 = | | = Real Application Case - ADAM-4117 = |
| | | |
− | '''<span style="font-size:large;">ADAM-4117 8-channel Analog Input Module</span>'''
| + | [[Real_Application_Case|Real Application Case: ADAM-4117]] |
− | | |
− | <span style="font-size:larger;">1. H.W. Environment & Configuration</span>
| |
− | | |
− | | |
− | | |
− | <span style="font-size:larger;">[[File:Adam-4117-01.png|600x560px|Adam-4117-01.png]]</span>
| |
− | | |
− | | |
− | | |
− | <span style="font-size:larger;">2. Setup Modbus register from ADAM utility: AdamApax .NET Utility</span>
| |
− | | |
− | <span style="font-size:larger;">2.1 Download AdamApax .NET Utility from URL [http://support.advantech.com/Support/DownloadSRDetail_New.aspx?SR_ID=1-2AKUDB&Doc_Source=Download http://support.advantech.com/Support/DownloadSRDetail_New.aspx?SR_ID=1-2AKUDB&Doc_Source=Download] and install it to your Gateway.</span>
| |
− | | |
− | <span style="font-size:larger;">2.2 Launch AdamApax .NET Utility, select COM port which ADAM module is connected, right click on the COM port you selected and click "Search Device" to detect your ADAM-4117.</span>
| |
− | | |
− | | |
− | | |
− | [[File:Adam-4117-04.png|680x500px|Adam-4117-04.png]] | |
− | | |
− | | |
− | | |
− | <span style="font-size:larger;">2.3 After ADAM-4117 appeared, click on it to check its settings or change the default settings for your H.W. configuration.</span>
| |
− | | |
− | [[File:Adam-4117-06.png|680x500px|Adam-4117-06.png]]
| |
− | | |
− | | |
− | | |
− | [[File:Adam-4117-07.png|680x500px|Adam-4117-07.png]]
| |
− | | |
− | | |
− | | |
− | [[File:Adam-4117-08.png|680x500px|Adam-4117-08.png]]
| |
− | | |
− | | |
− | | |
− | <span style="font-size:larger;">2.4 Provide a stable 12V voltage power to Vin0.</span>
| |
− | | |
− | [[File:Adam-4117-10.jpg|600x600px|Adam-4117-10.jpg]]
| |
− | | |
− | | |
− | | |
− | <span style="font-size:larger;">2.5 Check the value of Channel 0 from AdamApax .NET Utility, the value of Vin0 is 12.108V.</span>
| |
− | | |
− | [[File:Adam-4117-11.png|680x500px|Adam-4117-11.png]]
| |
− | | |
− | | |
− | | |
− | <span style="font-size:larger;">2.6 Check the value of Modbus Location 40001 from AdamApax .NET Utility, the value is 52900. ( 12.108 / 15 * 65536 = 52900.66 )</span>
| |
− | | |
− | [[File:Adam-4117-12.png|680x500px|Adam-4117-12.png]]
| |
− | | |
− | | |
− | | |
− | <span style="font-size:larger;">3. Gateway Modbus_Handler configuration</span>
| |
− | | |
− | <span style="font-size:larger;">3.1 Edit Modbus_Handler.ini for the ADAM's configuration.</span>
| |
− | <pre>[Platform]
| |
− | Interval=1
| |
− | #Interval: The time delay between two modbus access round in second.
| |
− | Delay=0
| |
− | #Delay: The time delay between two modbus access in millisecond.
| |
− | #Delay=0 means no delay.
| |
− | Log=0
| |
− | | |
− | Name=ADAM-4117
| |
− | Protocol=Modbus_RTU
| |
− | SlavePort=COM1
| |
− | Baud=9600
| |
− | Parity=None
| |
− | DataBits=8
| |
− | StopBits=1
| |
− | SlaveID=1
| |
− | </pre>
| |
− | | |
− | <span style="font-size:larger;">3.2 Edit Modbus_Handler.ini for ADAM-4117 modbus location configuration.</span>
| |
− | <pre>[Holding Registers]
| |
− | numberOfR=3
| |
− | R0=0,Vin0,0,65535,1,V,0,""
| |
− | R1=1,Vin1,0,65535,1,V,0,""
| |
− | R2=2,Vin2,0,65535,1,V,0,""
| |
− | | |
− | ;tag = offset, name, min, max, precision, unit, data type, lua script
| |
− | | |
− | ;tag Base Address
| |
− | ;B 00001-->Coils
| |
− | ;IB 10001-->Discrete Inputs
| |
− | ;IR 30001-->Input Registers
| |
− | ;R 40001-->Holding Registers
| |
− | | |
− | ;data type
| |
− | ;0->16-bit operation
| |
− | ;1->32-bit float no swap
| |
− | ;2->32-bit float byte and word swap
| |
− | ;3->32-bit float byte swap
| |
− | ;4->32-bit float word swap
| |
− | ;5->32-bit unsigned int no swap
| |
− | ;6->32-bit unsigned int word swap
| |
− | ;7->32-bit signed int no swap
| |
− | ;8->32-bit signed int word swap
| |
− | | |
− | </pre>
| |
− | | |
− | | |
− | | |
− | <span style="font-size:larger;">3.2 Restart WISE Agent service from Task Manager, login RMM 3.3 to check the values that ADAM-4117 and Gateway uploaded.</span>
| |
− | | |
− | <span style="font-size:larger;">[[File:Adam-4117-13 modbus 1.0.png|800x600px|Adam-4117-13.png]]</span>
| |
− | | |
− | | |
− | | |
− | <span style="font-size:larger;">3.3 Use Lua convert function to transfer modbus value to voltage value, open Modbus_Device0.ini and give Vin0~Vin2 Lua scripts as "modbus_val*15/65536".</span>
| |
− | <pre>[Holding Registers]
| |
− | numberOfR=3
| |
− | R0=0,Vin0,0,15,1,V,0,"modbus_val*15/65536"
| |
− | R1=1,Vin1,0,15,1,V,0,"modbus_val*15/65536"
| |
− | R2=2,Vin2,0,15,1,V,0,"modbus_val*15/65536"
| |
− | | |
− | ;tag = offset, name, min, max, precision, unit, data type, lua script
| |
− | | |
− | </pre>
| |
− | | |
− | | |
− | | |
− | <span style="font-size:larger;">3.4 Login RMM 3.3 again to check the values that ADAM-4117 and Gateway uploaded, the value is already converted to voltage value.</span>
| |
− | | |
− | <span style="font-size:larger;">[[File:Adam-4117-14 modbus 1.0.png|800x600px|Adam-4117-14.png]]</span>
| |
Revision as of 05:09, 7 August 2018
Introduction
Modbus enables communication among many devices connected to the same network, for example, a system that measures temperature and humidity and communicates the results to a computer. Modbus is often used to connect a supervisory computer with a remote terminal unit (RTU) in supervisory control and data acquisition (SCADA) systems.
Many of the data types are named from its use in driving relays: a single-bit physical output is called a coil, and a single-bit physical input is called a discrete input or a contact.
Modbus Service is a Windows/Linux system service for WISE Agent to read sensor data from Modbus device or write data into Modbus device. After sensor ata are acquired, WISE Agent will upload the data to the WISE-PaaS Cloud.
Configuration
1. Open File Explorer and change target folder to the RMM Agent installation folder.
2. Open and edit the file \module\module_config.xml to enable Modbus Handler
(by default, the path is C:\Program Files (x86)\Advantech\RMM 3.3 Agent\module\module_config.xml)
<ModuleName17>Modbus_Handler</ModuleName17>
<ModulePath17>\module\Modbus_Handler.dll</ModulePath17>
<ModuleEnable17>TRUE</ModuleEnable17>
3. Open and edit the file Mobus_Handler.ini
(by default, the path is C:\Program Files (x86)\Advantech\RMM 3.3 Agent\Mobus_Handler.ini)
3.1 Give a name for the filed "Name" in the [Platform] session.
3.2 Set the protocol for the field "Protocol" in the [Platform] session, you can config to the type of Modbus_TCP or Modbus_RTU follow below example:
Config for the modbus TCP devices:
Protocol=Modbus_TCP
ClientIP=(IP address of Modbus TCP devices)
ClientPort=(Port of Modbus TCP devices)
Example:
[Platform]
Name=WISE-4012E
Protocol=Modbus_TCP
ClientIP=127.0.0.1
ClientPort=502
UnitID=1
Interval=3
#Interval: The time delay between two modbus access round in second.
Delay=0
#Delay: The time delay between two modbus access in millisecond.
#Delay=0 means no delay.
Log=0
Config for the modbus RTU devices:
Protocol=Modbus_RTU
SlavePort=(The serial port's device node of the Gateway which connect to Modbus RTU devices)
Baud=(The baud rate for the serial port to communicate with Modbus RTU device)
Parity=(The parity of the serial port)
DataBits=(The data bits of the serial port)
StopBits=(The stop bits of the serial port)
Example:
[Platform]
Name=EKI-XXXX
Protocol=Modbus_RTU
SlavePort=COM1
Baud=19200
Parity=None
DataBits=8
StopBits=1
SlaveID=1
Interval=3
#Interval: The time delay between two modbus access round in second.
Delay=0
#Delay: The time delay between two modbus access in millisecond.
#Delay=0 means no delay.
Log=0
3.3 Set Modbus bits data and registers.
Example for Coils:
[Coils]
numberOfB=3
B0=0,LED0
B1=1,LED1
B2=2,LED2
Example for Discrete Inputs:
[Discrete Inputs]
numberOfIB=3
IB0=0,Switch0
IB1=1,Switch1
IB2=2,Switch2
EdgeSense Linux Docker version
How to config Modbus Service and Restart Service
$cd ${Installed path}/Installer/packages/Plugins/docker-edgesense-image-x86/EdgeSense/EService-Modbus/config
$sudo vim Modbus_Handler.ini
$sudo docker restart service-modbus
Real Application Case - ADAM-4117
Real Application Case: ADAM-4117