Difference between revisions of "Modbus Service"
Line 58: | Line 58: | ||
'''<span style="font-size:larger;">Example:</span>''' | '''<span style="font-size:larger;">Example:</span>''' | ||
− | <pre | + | <pre>[Platform] |
Name=WISE-4012E | Name=WISE-4012E | ||
Protocol=Modbus_TCP | Protocol=Modbus_TCP | ||
Line 65: | Line 65: | ||
Interval=3 | Interval=3 | ||
− | #Interval: The time delay between two modbus access round in second. | + | #Interval: The time delay between two modbus access round in second.; |
Delay=0 | Delay=0 | ||
#Delay: The time delay between two modbus access in millisecond. | #Delay: The time delay between two modbus access in millisecond. | ||
#Delay=0 means no delay. | #Delay=0 means no delay. | ||
Log=0 | Log=0 | ||
− | + | ||
</pre> | </pre> | ||
Line 98: | Line 98: | ||
'''<span style="font-size:larger;">Example:</span>''' | '''<span style="font-size:larger;">Example:</span>''' | ||
− | <pre | + | <pre>[Platform] |
Name=EKI-XXXX | Name=EKI-XXXX | ||
Protocol=Modbus_RTU | Protocol=Modbus_RTU | ||
Line 108: | Line 108: | ||
Interval=3 | Interval=3 | ||
− | #Interval: The time delay between two modbus access round in second. | + | #Interval: The time delay between two modbus access round in second.; |
Delay=0 | Delay=0 | ||
#Delay: The time delay between two modbus access in millisecond. | #Delay: The time delay between two modbus access in millisecond. | ||
#Delay=0 means no delay. | #Delay=0 means no delay. | ||
Log=0 | Log=0 | ||
− | + | ||
</pre> | </pre> | ||
Line 125: | Line 125: | ||
'''<span style="font-size:larger;">Device0 Example:</span>''' | '''<span style="font-size:larger;">Device0 Example:</span>''' | ||
− | <pre | + | <pre>[DeviceInfo] |
Name=Modbus_Device0 | Name=Modbus_Device0 | ||
Line 138: | Line 138: | ||
B0=0,LED0 | B0=0,LED0 | ||
B1=1,LED1 | B1=1,LED1 | ||
− | B2=2,LED2 | + | B2=2,LED2 |
− | |||
</pre> | </pre> | ||
+ | |||
+ | |||
Line 147: | Line 148: | ||
'''<span style="font-size:larger;">Device1 Example:</span>''' | '''<span style="font-size:larger;">Device1 Example:</span>''' | ||
− | <pre | + | <pre>[DeviceInfo] |
Name=Modbus_Device1 | Name=Modbus_Device1 | ||
Line 160: | Line 161: | ||
IB0=0,Switch0 | IB0=0,Switch0 | ||
IB1=1,Switch1 | IB1=1,Switch1 | ||
− | IB2=2,Switch2 | + | IB2=2,Switch2</pre> |
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
= EdgeSense Linux Docker version = | = EdgeSense Linux Docker version = |
Revision as of 07:20, 7 May 2018
Contents
Installation
1. Double click Agent_Modbus_Handler_2.0.0.exe to start installation.
2. Click "Next" on the Welcome screen.
3. Select Installation Folder and then click "Next" to continue.
4. Click "Install" on the Ready to Install screen to continue.
5. Installation completed, click "Finish" button to exit the Setup Wizard.
Configuration
1. Open File Explorer and change target folder to the Modbus Service installation folder.
2. Open and edit the file Mobus_Handler.ini
2.1 Give a Name for the platform.
2.2 Set the Protocol.
For the modbus TCP devices:
Protocol=Modbus_TCP
ClientIP=(IP address of Modbus TCP devices)
ClientPort=(Port of Modbus TCP devices)
Example:
[Platform] Name=WISE-4012E Protocol=Modbus_TCP ClientIP=127.0.0.1 ClientPort=502 Interval=3 #Interval: The time delay between two modbus access round in second.; Delay=0 #Delay: The time delay between two modbus access in millisecond. #Delay=0 means no delay. Log=0
For the modbus RTU devices:
Protocol=Modbus_RTU
SlavePort=(The serial port's device node of the gateway which connect to Modbus RTU devices)
Baud=(The baud rate of the serial port)
Parity=(The parity of the serial port)
DataBits=(The data bits of the serial port)
StopBits=(The stop bits of the serial port)
Example:
[Platform] Name=EKI-XXXX Protocol=Modbus_RTU SlavePort=COM1 Baud=19200 Parity=None DataBits=8 StopBits=1 Interval=3 #Interval: The time delay between two modbus access round in second.; Delay=0 #Delay: The time delay between two modbus access in millisecond. #Delay=0 means no delay. Log=0
2.3 Set the number of modbus devices and device detail information file.
Device0 Example:
[DeviceInfo] Name=Modbus_Device0 # For Modbus_TCP UnitID=1 # For Modbus_RTU #SlaveID=1 [Coils] numberOfB=3 B0=0,LED0 B1=1,LED1 B2=2,LED2
Device1 Example:
[DeviceInfo] Name=Modbus_Device1 # For Modbus_TCP UnitID=2 # For Modbus_RTU #SlaveID=2 [Discrete Inputs] numberOfIB=3 IB0=0,Switch0 IB1=1,Switch1 IB2=2,Switch2
EdgeSense Linux Docker version
How to config Modbus Service and Restart Service
$cd ${Installed path}/Installer/packages/Plugins/docker-edgesense-image-x86/EdgeSense/EService-Modbus/config $sudo vim Modbus_Handler.ini $sudo docker restart service-modbus
JSON Format for upload data
{ "Modbus_Handler":{ "Platform":{ "bn":"Platform", "e":[{"n":"Version","sv":"2.0.0"}, {"n":"Description","sv":"This service is Modbus Service"}, {"n":"Protocol","sv":"Modbus_TCP"}, {"n":"Name","sv":"WISE-4012E"}, {"n":"ClientIP","sv":"127.0.0.1"}, {"n":"ClientPort","sv":"502"}, {"n":"Connection","bv":true}] }, "Modbus_Device0":{ "bn":"Modbus_Device0", "e":[{"n":"UnitID","sv":"1"}], "Coils":{ "bn":"Coils", "e":[{"n":"LED0","bv":true}, {"n":"LED1","bv":true}, {"n":"LED2","bv":false}] } }, "Modbus_Device1":{ "bn":"Modbus_Device1", "e":[{"n":"UnitID","sv":"2"}], "Discrete Inputs":{ "bn":"Discrete Inputs", "e":[{"n":"Switch0","bv":false}, {"n":"Switch1","bv":true}, {"n":"Switch2","bv":false}] } } } }