= Introduction =
  
Alarm event that is a service to subscribe MQTT borker topic to get message code.  
+
Alarm event that is a service to subscribe MQTT borker topic to get message code.
  
Accroding to message code mapping event message and send event to EI server. Event message is setting in the "event_config.json". It can set handler name, tag name, event code to subscribe. 
+
Accroding to message code mapping event message and send event to EI server. Event message is setting in the "event_config.json".  
 +
 
 +
And event_config.json that can set handler name, tag name to subscribe specific handler and item value.
  
 
= Alarm Event =
 
= Alarm Event =

Revision as of 11:07, 28 November 2018

Introduction

Alarm event that is a service to subscribe MQTT borker topic to get message code.

Accroding to message code mapping event message and send event to EI server. Event message is setting in the "event_config.json".

And event_config.json that can set handler name, tag name to subscribe specific handler and item value.

Alarm Event

AlarmEvent Architecture.jpg

How to

Software Requirements

  • MQTT broker  V1.0.3
  • EI Agent
  • Agent_Modbus_Handler_2.0.1-rc2 or newer

Installation

1.Double click AlarmEvent-X.X.X.exe to install.

2.Click "Next" to continue the setup wizard.

3.Select installation folder then click "Next"

4.Click "Next" to begin the installation

5.Complete the installation, click "Finish" to exit the setup wizard

6.Edit event_config.json (if need)

7.Restart device

Configuration​

event_config.json (location: C:\Program Files (x86)\Advantech\AlarmEvent\config)

  • handler_name: Subcribe handler name
  • tag_name: Subcribe tag name
  • subtype: Event subtype
  • event:
    1. severity: Emergency = 0 ,Warning = 4
    2. msg_code: Device output code 
    3. msg: Output code express message
    4. error_code: Output code express error code
    5. extmsg: Externel event message
  • server: MQTT broker ip
  • server_port:  MQTT broker port
{
    "handler_name":"Modbus_Handler",   
    "tag_name":"Error_Code",
    "subtype":"TC_AC",

    "event":
    {
        "1": {"severity":0, "msg_code":241, "msg":"Door Open","error_code": "E:0030", "extmsg":"Immediate stop: Enclosure door open"},
        "2": {"severity":4, "msg_code":242, "msg":"Door Open", "error_code": "A:0030","extmsg":"Warning: Enclosure door open"},
        "3": {"severity":4, "msg_code":250, "msg":"CAB FTR DP ALM","error_code": "A:0031", "extmsg":"Warning: Cabinet filter differential pressure"},
        "4": {"severity":0, "msg_code":321, "msg":"Oil level","error_code": "E:0040", "extmsg":"Immediate stop: Oil level alarm"},
        "5": {"severity":4, "msg_code":322, "msg":"Oil level alarm","error_code": "A:0040", "extmsg":"Warning: Oil level high"},
        "6": {"severity":0, "msg_code":401, "msg":"RD alarm","error_code": "E:0050", "extmsg":"Immediate stop: Refrigerant dryer"},
        "7": {"severity":4, "msg_code":402, "msg":"RD alarm","error_code": "A:0050", "extmsg":"Warning: Refrigerant dryer"},
        "8": {"severity":0, "msg_code":481, "msg":"Belt drive SERV","error_code": "E:0060", "extmsg":"Immediate stop: Belt drive service"},
        "9": {"severity":0, "msg_code":561, "msg":"Fan MTR IMM stop","error_code": "E:0070", "extmsg":"Immediate stop: Fan motor trip"}
    },       

    "server":"127.0.0.1",
    "server_port": 3000
}

Import event table

  • Add RMM_Event data source

AlarmEvent dashboard 1.JPG


  • Upload plugin (swanair-datatable-panel_2018-11-21.zip)

AlarmEvent dashboard 5.JPG


  • Add panel

AlarmEvent dashboard 6.JPG


  • Panel setting

AlarmEvent dashboard 4.JPG


  • Event table

AlarmEvent dashboard 7.JPG

Json Data Format

{
     "susiCommData":
     {
       "commCmd":2059,
       "requestID":2001,
       "agentID":"Modbus_Handler",
       "handlerName":"general",
       "sendTS":1541992952337,
       "eventnotify":
       {
         "subtype":"TC_AC",
         "msg":"Door Open",
         "severity":4,
         "handler":"Modbus_Handler",
         "extMsg":
         {
           "n": "Warning: Enclosure door open",
           "ErrorCode":"A:0030",
           "eventID":242
         }
       }
     }
}