Modbus Handler Service+ EIServiceSDK

From ESS-WIKI
Revision as of 08:20, 28 December 2017 by Hank.peng (talk | contribs)
Jump to: navigation, search

Overview


SNTest.exe is a demo program to show how to use EIService SDK API to do a Modbus data read action from Modbus register or data write action to the register.




Modbus Simulator


Start ModSim32 and configure the register for the demonstration:


Set Holding Register data address: 0001 (From first Holding Register address)

Set Length: 8

Set data from address 40001 ~ 40008, for example 101, 102 , 103 …


[[File:|720x406px]]





WISE Agent and Modbus Plugin


Configure Modbus Plugin settings (Modbus_Handler.ini) as showed below for the demonstrations:


[Platform]

Name=WISE-4012E

Protocol=Modbus_TCP

ClientIP=127.0.0.1

ClientPort=502

UnitID=1

Interval=1

#Interval: The time delay between two modbus access round in second.

Delay=0

#Delay: The time delay between two modbus access in millisecond.

#Delay=0 means no delay.

Log=0


[Holding Registers]

numberOfR=3

R0=0,Data0,-1000000,1000000,1,V,0,""

R1=1,Data1,-1000000,1000000,1,V,0,""

R2=2,Data2,-1000000,1000000,1,V,0,""


;tag = offset, name, min, max, precision, unit, data type, lua script




Demo Program


Run SNTest.exe and select item 5) Set Service’s Action.


[[File:|714x444px]]




  1. To do a data Write Demonstration, please set the Service Name, Plugin Name, Sensor Name, Data Type and the value of Data that you want to write, for example


Service Name: Modbus_Handler

Plugin Name: Modbus_Handler

Sensor Name: Modbus_Handler/Holding Registers/Data0

Data Type: v

Data: 66


After completed the procedure, the numbers will be written into assigned variable by EIService SDK function.


[[File:|812x465px]]




  1. You can check ModSim32 screen to confirm the procedure of data write.


[[File:|683x463px]]


(End)