Introduction

Modbus enables communication among many devices connected to the same network, for example, a system that measures temperature and humidity and communicates the results to a computer. Modbus is often used to connect a supervisory computer with a remote terminal unit (RTU) in supervisory control and data acquisition (SCADA) systems.

Many of the data types are named from its use in driving relays: a single-bit physical output is called a coil, and a single-bit physical input is called a discrete input or a contact.

Modbus Service is a Windows/Linux system service for WISE Agent to read sensor data from Modbus device or write data into Modbus device. After sensor ata are acquired, WISE Agent will upload the data to the WISE-PaaS Cloud.

Modbus Service

JSON Format for upload data

{
   "Modbus_Handler":{
      "Platform":{
         "bn":"Platform",
         "e":[{"n":"Version","sv":"2.0.0"},
              {"n":"Description","sv":"This service is Modbus Service"},
              {"n":"Protocol","sv":"Modbus_TCP"},
              {"n":"Name","sv":"WISE-4012E"},
              {"n":"ClientIP","sv":"127.0.0.1"},
              {"n":"ClientPort","sv":"502"},
              {"n":"Connection","bv":true}]
      },
      "Modbus_Device0":{
         "bn":"Modbus_Device0",
         "e":[{"n":"UnitID","sv":"1"}],
         "Coils":{
            "bn":"Coils",
            "e":[{"n":"LED0","bv":true},
                 {"n":"LED1","bv":true},
                 {"n":"LED2","bv":false}]
         }
      },
      "Modbus_Device1":{
         "bn":"Modbus_Device1",
         "e":[{"n":"UnitID","sv":"2"}],
         "Discrete Inputs":{
            "bn":"Discrete Inputs",
            "e":[{"n":"Switch0","bv":false},
                 {"n":"Switch1","bv":true},
                 {"n":"Switch2","bv":false}]
         }
      }
   }
}

How To

Installation

1. Double click Agent_Modbus_Handler_2.0.0.exe to start installation.

2. Click "Next" on the Welcome screen.

Agent modbus handler 02.png


3. Select Installation Folder and then click "Next" to continue.

Agent modbus handler 03.png


4. Click "Install" on the Ready to Install screen to continue.

Agent modbus handler 04.png


5. Installation completed, click "Finish" button to exit the Setup Wizard.

Agent modbus handler 06.png


Configuration

1. Open File Explorer and change target folder to the Modbus Service installation folder.

2. Open and edit the file Mobus_Handler.ini

2.1 Give a Name for the platform.

2.2 Set the Protocol.

For the modbus TCP devices:

Protocol=Modbus_TCP

ClientIP=(IP address of Modbus TCP devices)

ClientPort=(Port of Modbus TCP devices)  

Modbus_Handler.ini Example:

[Platform]
Name=WISE-4012E
Protocol=Modbus_TCP
ClientIP=127.0.0.1
ClientPort=502

Interval=3
#Interval: The time interval of modbus data access/report cycle in second.
Delay=0
#Delay: The time delay between two modbus address R/W in millisecond.
#Delay=0 means no delay.
Log=0

[Devices]
numberOfDevices=2
Device0=Modbus_Device0.ini
Device1=Modbus_Device1.ini


For the modbus RTU devices:

Protocol=Modbus_RTU

SlavePort=(The serial port's device node of the Gateway which connect to Modbus RTU devices)

Baud=(The baud rate for the serial port to communicate with Modbus RTU device)

Parity=(The parity of the serial port)

DataBits=(The data bits of the serial port)              

StopBits=(The stop bits of the serial port) 


Example:

[Platform]
Name=EKI-XXXX
Protocol=Modbus_RTU
SlavePort=COM1
Baud=19200
Parity=None
DataBits=8
StopBits=1

Interval=3
#Interval: The time interval of modbus data access/report cycle in second.
Delay=0
#Delay: The time delay between two modbus address R/W in millisecond.
#Delay=0 means no delay.
Log=0

[Devices]
numberOfDevices=2
Device0=Modbus_Device0.ini
Device1=Modbus_Device1.ini


2.3 Set Modbus devices detail configuration.

Modbus_Device0.ini Example:

[DeviceInfo]
# For Modbus_TCP
UnitID=1
# For Modbus_RTU
#SlaveID=1

[Coils]
numberOfB=3
B0=0,LED0
B1=1,LED1
B2=2,LED2


Modbus_Device1.ini Example:


[DeviceInfo]
# For Modbus_TCP
UnitID=2
# For Modbus_RTU
#SlaveID=2

[Discrete Inputs]
numberOfIB=3
IB0=0,Switch0
IB1=1,Switch1
IB2=2,Switch2

[Input Registers]
numberOfIR=3
IR0=0,Data0,-1000000,1000000,1,V,0,""
IR1=1,Data1,-1000000,1000000,1,V,0,""
IR2=2,Data2,-1000000,1000000,1,V,0,""


Docker version

To config Modbus Service and Restart Service in EdgeSense v1.0.2 Docker version:

$cd ${Installed path}/Installer/packages/Plugins/docker-edgesense-image-x86/EdgeSense/EService-Modbus/config
$sudo vim Modbus_Handler.ini
$sudo docker restart service-modbus


Real Application Case: ADAM-4117


Release

This is an overview that displays Modbus Service versions and some stats and numbers for each release.

Index Version Date Platform OS Release Note
1 v2.0.0 2018/5/17 x86_64 CPU Windows  Agent_Modbus_Handler Release Note v2.0.0
2 v2.0.1 2018/9/6 x86_64 CPU
Windows
Agent_Modbus_Handler Release Note v2.0.1