Modbus Handler Service+ EIServiceSDK

From ESS-WIKI
Revision as of 08:16, 28 December 2017 by Hank.peng (talk | contribs)
Jump to: navigation, search

<parsererror style="display: block; white-space: pre; border: 2px solid #c77; padding: 0 1em 0 1em; margin: 1em; background-color: #fdd; color: black">

This page contains the following errors:

error on line 1 at column 4311: attributes construct error

Below is a rendering of the page up to the first error.

</parsererror> Overview


SNTest.exe is a demo program to show how to use EIService SDK API to do a Modbus data read action from Modbus register or data write action to the register.




Modbus Simulator


Start ModSim32 and configure the register for the demonstration:


  • Set Holding Register data address: 0001 (From first Holding Register address)
  • Set Length: 8
  • Set data from address 40001 ~ 40008, for example 101, 102 , 103 …


Modsim32 01.png







WISE Agent and Modbus Plugin


Configure Modbus Plugin settings (Modbus_Handler.ini) as showed below for the demonstrations:


[Platform]

Name=WISE-4012E

Protocol=Modbus_TCP

ClientIP=127.0.0.1

ClientPort=502

UnitID=1

Interval=1

#Interval: The time delay between two modbus access round in second.

Delay=0

#Delay: The time delay between two modbus access in millisecond.

#Delay=0 means no delay.

Log=0


[Holding Registers]

numberOfR=3

R0=0,Data0,-1000000,1000000,1,V,0,""

R1=1,Data1,-1000000,1000000,1,V,0,""

R2=2,Data2,-1000000,1000000,1,V,0,""


;tag = offset, name, min, max, precision, unit, data type, lua script




Demo Program