Modbus Handler v1.0

From ESS-WIKI
Revision as of 04:54, 7 August 2018 by Hank.peng (talk | contribs)
Jump to: navigation, search

Introduction

Modbus enables communication among many devices connected to the same network, for example, a system that measures temperature and humidity and communicates the results to a computer. Modbus is often used to connect a supervisory computer with a remote terminal unit (RTU) in supervisory control and data acquisition (SCADA) systems.

Many of the data types are named from its use in driving relays: a single-bit physical output is called a coil, and a single-bit physical input is called a discrete input or a contact.

Modbus Service is a Windows/Linux system service for WISE Agent to read sensor data from Modbus device or write data into Modbus device. After sensor ata are acquired, WISE Agent will upload the data to the WISE-PaaS Cloud.



Configuration

1. Open File Explorer and change target folder to the RMM Agent installation folder. 

2. Open and edit the file \module\module_config.xml to enable Modbus Handler

   (by default, the path is C:\Program Files (x86)\Advantech\RMM 3.3 Agent\module\module_config.xml)

<?xml version="1.0" encoding="utf-8" standalone="yes"?>
<XMLConfigSettings>
    <BaseSettings>
        <ModuleNum>15</ModuleNum>
        <ModuleName1>HDDHandler</ModuleName1>
        <ModulePath1>\module\HDDHandler.dll</ModulePath1>
        <ModuleEnable1>FALSE</ModuleEnable1>
        ...
	<ModuleName17>Modbus_Handler</ModuleName17>
	<ModulePath17>\module\Modbus_Handler.dll</ModulePath17>
	<ModuleEnable17>'''TRUE'''</ModuleEnable17>		
    </BaseSettings>
</XMLConfigSettings>

3. Open and edit the file Mobus_Handler.ini

    (by default, the path is C:\Program Files (x86)\Advantech\RMM 3.3 Agent\Mobus_Handler.ini)

3.1 Give a name for the filed "Name" in the [Platform] session.

3.2 Set the protocol for the field "Protocol" in the [Platform] session, you can config to the type of Modbus_TCP or Modbus_RTU follow below example:

Config for the modbus TCP devices:

Protocol=Modbus_TCP

ClientIP=(IP address of Modbus TCP devices)

ClientPort=(Port of Modbus TCP devices)  

Example:


[Platform]
Name=WISE-4012E
Protocol=Modbus_TCP
ClientIP=127.0.0.1
ClientPort=502
UnitID=1

Interval=3
#Interval: The time delay between two modbus access round in second.
Delay=0
#Delay: The time delay between two modbus access in millisecond.
#Delay=0 means no delay.
Log=0


Config for the modbus RTU devices:

Protocol=Modbus_RTU

SlavePort=(The serial port's device node of the Gateway which connect to Modbus RTU devices)

Baud=(The baud rate for the serial port to communicate with Modbus RTU device)

Parity=(The parity of the serial port)

DataBits=(The data bits of the serial port)              

StopBits=(The stop bits of the serial port) 


Example:

[Platform]
Name=EKI-XXXX
Protocol=Modbus_RTU
SlavePort=COM1
Baud=19200
Parity=None
DataBits=8
StopBits=1
SlaveID=1

Interval=3
#Interval: The time delay between two modbus access round in second.
Delay=0
#Delay: The time delay between two modbus access in millisecond.
#Delay=0 means no delay.
Log=0


3.3 Set Modbus bits data and registers.

Example for Coils:

[Coils]
numberOfB=3
B0=0,LED0
B1=1,LED1
B2=2,LED2


Example for Discrete Inputs:

[Discrete Inputs]
numberOfIB=3
IB0=0,Switch0
IB1=1,Switch1
IB2=2,Switch2

EdgeSense Linux Docker version

How to config Modbus Service and Restart Service

$cd ${Installed path}/Installer/packages/Plugins/docker-edgesense-image-x86/EdgeSense/EService-Modbus/config
$sudo vim Modbus_Handler.ini
$sudo docker restart service-modbus


Real Application Case - ADAM-4117

ADAM-4117 8-channel Analog Input Module

1. H.W. Environment & Configuration


Adam-4117-01.png


2. Setup Modbus register from ADAM utility: AdamApax .NET Utility

2.1 Download AdamApax .NET Utility from URL http://support.advantech.com/Support/DownloadSRDetail_New.aspx?SR_ID=1-2AKUDB&Doc_Source=Download and install it to your Gateway.

2.2 Launch AdamApax .NET Utility, select COM port which ADAM module is connected, right click on the COM port you selected and click "Search Device" to detect your ADAM-4117.


Adam-4117-04.png


2.3 After ADAM-4117 appeared, click on it to check its settings or change the default settings for your H.W. configuration.

Adam-4117-06.png


Adam-4117-07.png


Adam-4117-08.png


2.4 Provide a stable 12V voltage power to Vin0.

Adam-4117-10.jpg


2.5 Check the value of Channel 0 from AdamApax .NET Utility, the value of Vin0 is 12.108V.

Adam-4117-11.png


2.6 Check the value of Modbus Location 40001 from AdamApax .NET Utility, the value is 52900. ( 12.108 / 15 * 65536 = 52900.66 )

Adam-4117-12.png


3. Gateway Modbus_Handler configuration

3.1 Edit Modbus_Handler.ini for the ADAM's configuration.

[Platform]
Interval=1
#Interval: The time delay between two modbus access round in second. 
Delay=0
#Delay: The time delay between two modbus access in millisecond.
#Delay=0 means no delay.
Log=0

Name=ADAM-4117
Protocol=Modbus_RTU
SlavePort=COM1
Baud=9600
Parity=None
DataBits=8
StopBits=1
SlaveID=1

3.2 Edit Modbus_Handler.ini for ADAM-4117 modbus location configuration.

[Holding Registers]
numberOfR=3
R0=0,Vin0,0,65535,1,V,0,""
R1=1,Vin1,0,65535,1,V,0,""
R2=2,Vin2,0,65535,1,V,0,""

;tag = offset, name, min, max, precision, unit, data type, lua script

;tag    Base Address
;B    00001-->Coils
;IB    10001-->Discrete Inputs
;IR    30001-->Input Registers
;R    40001-->Holding Registers

;data type
;0->16-bit operation
;1->32-bit float no swap
;2->32-bit float byte and word swap
;3->32-bit float byte swap
;4->32-bit float word swap
;5->32-bit unsigned int no swap
;6->32-bit unsigned int word swap
;7->32-bit signed int no swap
;8->32-bit signed int word swap


3.2 Restart WISE Agent service from Task Manager, login RMM 3.3 to check the values that ADAM-4117 and Gateway uploaded.

Adam-4117-13.png


3.3 Use Lua convert function to transfer modbus value to voltage value, open Modbus_Device0.ini and give Vin0~Vin2 Lua scripts as "modbus_val*15/65536".

[Holding Registers]
numberOfR=3
R0=0,Vin0,0,15,1,V,0,"modbus_val*15/65536"
R1=1,Vin1,0,15,1,V,0,"modbus_val*15/65536"
R2=2,Vin2,0,15,1,V,0,"modbus_val*15/65536"

;tag = offset, name, min, max, precision, unit, data type, lua script


3.4 Login RMM 3.3 again to check the values that ADAM-4117 and Gateway uploaded, the value is already converted to voltage value.

Adam-4117-14.png